1. Sheet press not heating or heating slowly
-
Check there’s no ‘STOP’ on the associated PID Controller.
→ Switch to
RUNmode on the PID Controller (cycle through the menu by tapping the second button from the right on the PID Controller). TheOUTindicator should be on (relay active) andSTOPindicator should be off.
→ As an alternative, in the dashboard section, under Commons, All Stop can be used to switch to “RUN” mode
- Disable
Sequential Heatingin the dashboard section (if applicable)
- Ensure that the correct temperature sensor is connected to the PID Controller
1.1 PID controllers not accepting new temperature setpoints
- Check that ‘Command Write Mode’ is enabled (use the first 2 buttons from the left on the PID Controller to cycle through the menu).
- As an alternative, in the dashboard section, under
Commons,Command Write Modecan be toggled to override the command write mode for all enabled PID Controllers.